Detection of polychlorinated biphenyls contaminated power transformers in Sri Lanka

dc.contributor.authorDissanayake, D.A.T.W.K.
dc.contributor.authorWeeraman, P.I.D.
dc.contributor.authorAberathna, A.H.M.A.K.
dc.contributor.authorHettiarachchi, N.B.
dc.contributor.authorPiyathissa, D.K.S.D.
dc.contributor.authorLiyanaarachchi, V.V.
dc.contributor.authorMubarak, M.N.A.
dc.contributor.authorHemarathne, J.D.K.G.
dc.contributor.authorWerahera, S.M.
dc.date.accessioned2026-01-19T06:43:38Z
dc.date.available2026-01-19T06:43:38Z
dc.date.issued2021-10-29
dc.description.abstractPolychlorinated biphenyls (PCBs) classified under persistent organic pollutants are a group I carcinogen. Aroclors were one of the widely used and most reported PCB commercial mixtures globally. Aroclor 1260, Aroclor 1254, Aroclor 1242, and Aroclor 1016 have been used in transformers. Sri Lanka is a signatory of the Stockholm Convention, where PCB usage has been curtailed since 2005. PCBs have mainly been used as insulating oil in transformers and capacitors. The elimination of PCBs by 2025 is a primary goal set by the convention. Accordingly, analysing and inventorying the transformers contaminated with greater than 50 mg kg⁻¹ PCBs in Sri Lanka is in progress. This study developed a method based on the ASTM D 4059 to determine the PCB content in insulating oils. PCBs in the sample were extracted with 2,2,4-trimethylpentane followed by interference removal using activated magnesium silicate. The extracted sample was allowed to stand for 10 min to settle the magnesium silicate particles, and 1.0 mL of the supernatant and 0.1 mL of hexachlorobenzene were mixed and analysed with gas chromatography- electron capture detection (GC-ECD). A matrix-matched calibration was used to address the intensity suppression due to the mineral oil, and ratios of uniquely identified well-resolved peaks were used in quantification by adding an internal standard to both calibrators and samples. The Ceylon Electricity Board inventory has more than 30,000 transformers, of which 2,500 were screened as suspected transformers to date. The confirmatory analysis was carried out in 329 samples by GC-ECD. Some of the samples (16.4%) contained total PCBs greater than 50 mg kg¹ , out of which 16.1% had Aroclor 1260, and 1.5% contained both Aroclor 1260 and Aroclor 1254. The findings will be included in the national inventory facilitating PCB mitigation programs following the Stockholm Convention.
dc.description.sponsorshipFinancial assistance from the Ministry of Environment, Sri Lanka, and UNIDO (Grant No. 150050) is acknowledged.
dc.identifier.citationProceedings of the Postgraduate Institute of Science Research Congress (RESCON) -2021, University of Peradeniya, P 158
dc.identifier.isbn978-955-8787-09-0
dc.identifier.urihttps://ir.lib.pdn.ac.lk/handle/20.500.14444/7476
dc.language.isoen_US
dc.publisherPostgraduate Institute of Science (PGIS), University of Peradeniya, Sri Lanka
dc.subjectAroclors
dc.subjectInsulating oil
dc.subjectPCBs
dc.subjectStockholm Convention
dc.subjectTransformers
dc.titleDetection of polychlorinated biphenyls contaminated power transformers in Sri Lanka
dc.title.alternativePhysical Sciences
dc.typeArticle

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Dissanayake, D.A.T.W.K.pdf
Size:
159.22 KB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed to upon submission
Description:

Collections